KYNS58-12 Medium-Voltage Dual-Loop Switchgear
KYNS58-12 Medium-Voltage Dual-Loop Switchgear is suitable for 3.6-12kV three-phase AC 50Hz power grids, and is used to receive and distribute electrical energy, as well as control, monitor, and protect circuits. The KYNS58-12 dual-loop outgoing cabinet independently developed and manufactured by the Company can replace traditional outgoing cabinets, with each cabinet capable of achieving two outgoing lines, greatly saving space and investment costs. Meanwhile, it also has complete and reliable anti-misoperation functions. It is a new choice for KYN switchgears to meet customers’ new demands.
- Overview
- Recommended Products
Product Overview:
KYNS58-12 Medium-Voltage Dual-Loop Switchgear is suitable for 3.6-12kV three-phase AC 50Hz power grids, and is used to receive and distribute electrical energy, as well as control, monitor, and protect circuits. The KYNS58-12 dual-loop outgoing cabinet independently developed and manufactured by the Company can replace traditional outgoing cabinets, with each cabinet capable of achieving two outgoing lines, greatly saving space and investment costs. Meanwhile, it also has complete and reliable anti-misoperation functions. It is a new choice for KYN switchgears to meet customers’ new demands.
Specifications and Parameters:
S/N |
Name |
Unit |
Data |
1 |
Rated voltage |
kV |
12 |
2 |
Rated current |
A |
630-3150 |
3 |
Rated frequency |
Hz |
50 |
4 |
Rated short-circuit breaking current |
kA |
40 |
5 |
Rated short-circuit breaking current |
kA |
40 |
6 |
Rated short-circuit making current (peak) |
kA |
100 |
7 |
Rated short-time withstand current duration |
s |
4 |
8 |
Rated short-time withstand current (main loop) |
kA |
40 |
9 |
Rated peak value withstand current (main loop) |
kA |
100 |
10 |
Rated peak withstand current (ground loop) |
kA |
86.6 |
11 |
Rated short-time power frequency withstand voltage |
kV/1min |
42 |
12 |
Rated lightning impulse withstand voltage |
kV |
75 |
13 |
Rated short-time power frequency withstand voltage (break) |
kV/1min |
48 |
14 |
Rated lightning impulse withstand voltage (fracture) |
kV |
85 |
15 |
Mechanical life |
Times |
10000 |
Product Features:
❖ KYNS58-12 Medium-Voltage Dual-Loop Switchgear is a high-voltage outgoing cabinet developed by our company to meet the requirements of low user budgets and limited installation space.
❖ The product features a bolted enclosure with high mechanical strength, ensuring neatness and aesthetic appeal.
❖ It significantly saves space while reducing construction costs.